Modular Block System: Hydraulic Presses

6-101

- Bit 04:

Input parameter

MP1 or MP2 has changed, while input

parameter

Toff = 1

Remedy: Check muting inputs, cable, input card and all
conditions, and then reset.

- Bit 05:

Muting signal MP1 or MP2 was not in its start position
Remedy: Check muting inputs, cable, input card and all
conditions, and then reset.

- Bit 06:

Synchronisation time (input parameter

TPSy) for MP1/MP2

exceeded
Remedy: Check muting inputs, cable and input card, then
reset (input parameter

RSET).

- Bit 07:

Max. interrupt time (input parameter

TInt) for MP1/MP2

exceeded
Remedy: Check muting inputs, cable, input card and all
conditions, and then reset.

- Bit 09:

Time from input parameter

TS12 exceeded

The time between the operation of muting signals MS1 and
MS2 or
the time between the operation of muting signals MS1 (MS2)
and the release of MS1 has been exceeded.
Remedy: Check muting inputs, cable, input card and all
conditions, and then reset.

- Bit 10:

ESPE/AOPD interrupted
Remedy: Clear protected field and then reset.

- Bit 11:

Muting time exceeded (input parameter

TMut)

Remedy: Check the run time required for the vehicle to travel
through the muting zone.

- Bit 12:

TOPD exceeded
The time from “Muting Start” to “ESPE/AOPD interrupted” or
the time from “Muting Signal ended” to “ESPE/AOPD clear”
has been exceeded. There are a number of potential reasons
for this, for example:
- Vehicle stationary within muting zone
- ESPE/AOPD not reacting
Remedy: Depends on the error.

- Bit 13:

1/0-pulse edge from MS2 while MS1 = 1 (MS2 returning to
sequential mode)
Remedy: Check muting inputs, cable, input card and all
conditions, and then reset.