Output parameters, Standard function blocks, Sb088 – Pilz PSS SB HYD, Basic license User Manual
Page 200

6-138
Modular Block System: Hydraulic Presses
Standard Function Blocks
•
VTyp:
Type of valve to be monitored
VTyp = 0:
Monitoring a directional control valve
VTyp = 1:
Monitoring a poppet valve
(see also under “Function”)
•
RSET:
Error reset
RSET = 0/1 pulse edge: Reset fault
It will only be possible to reset an existing fault if
the valve is in its start (off) position (valve de-
energised and acknowledgement from valve is
present) and no start signal is present (
ON •1).
Output parameters
•
ENBL:
Enable flag bit
ENBL = 0: Enable locked
When the valves are switched off (input parameter
ON = 1/0 pulse edge), the enable is locked until
the valves return to their start position (input
parameter
S1 = 1 and S2 = 1). This is not an error.
The block will cancel the enable immediately if it
detects a fault.
ENBL = 1: Enable
The block will set the enable if no fault has been
found and the valves are either in operation or in
their start position.
•
Y1:
Output parameters for operating valve Y1
Y1 = 0:
Valve Y1 off
Y1 = 1:
Valve Y1 on
•
Y2:
Output parameter for operating valve Y2
Y2 = 0:
Valve Y2 off
Y2 = 1:
Valve Y2 on
•
ERR:
This output parameter is set as soon as a fault is discovered.
ERR = 0:
No fault found
ERR = 1:
Fault found
SB088
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license