Blocks required, Standard function blocks, Sb067 – Pilz PSS SB HYD, Basic license User Manual
Page 118

6-56
Modular Block System: Hydraulic Presses
Standard Function Blocks
- Bit 06:
Faults which occur as the pulse edge changes at the input
parameter
EIN
Faults which occur as the pulse edge changes at the inputRFK
2 interrupted
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 07:
Faults which occur as the pulse edge changes at the input
parameter
EIN
RFK 2 closed
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 08:
Faults which occur as the pulse edge changes at the input
parameter
EIN
Reset input constantly high or set too early
Remedy: Release reset button and press it again. If this does
not work, check contacts, cable, input card and all conditions
and then reset (input parameter
RSET)
• Error messages on the CPU-display
- None
Global parameters used in administration data block DB015
Global parameters may be set in OB120 using SB070.
• DW1002: Number of cycles for reaction time of RFK
Blocks required
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.
• SB070
Initialisation of global parameters in DB015
SB067
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license