Blocks required – Pilz PSS SB HYD, Basic license User Manual
Page 219

Modular Block System: Hydraulic Presses
6-157
- Bit 12:
No signal change detected from input parameter
S1.
During the working cycle of valve Y1 (valve switching on and
off), the valve has retained its start position (valve de-
energised, acknowledgement present).
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 13:
No signal change detected from input parameter
S2.
During the working cycle of valve Y2 (valve switching on and
off), the valve has retained its start position (valve de-
energised, acknowledgement present).
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 14:
Invalid time entered under input parameter
TOn
Remedy: Enter a permitted value (for details of value range
see input parameter
TOn).
- Bit 15:
Invalid time entered under input parameter
TOff
Remedy: Enter a permitted value (for details of value range
see input parameter
TOff).
• Error messages on the CPU-display
- None
Global parameters used in administration data block DB015
Global parameters may be set in OB120 using SB070.
• DW1022: PSS scan time
Blocks required
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license