Modular Block System: Hydraulic Presses
Standard Function Blocks
SB072
SB072: Temporary suspension of safety functions
(ESPE/AOPD muting)
Block header
Input parameters
•
SSNR:
Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).
•
NO_1:
N/O contact 1 of ESPE/AOPD
NO_1 = 0: Protected field broken
NO_1 = 1: Protected field clear
•
NO_2:
N/O contact 2 of ESPE/AOPD
NO_2 = 0: Protected field broken
NO_2 = 1: Protected field clear
•
MS1:
N/O contact of Muting signal Serial 1
MS1 = 0:
Not operated (muting signal off)
MS1 = 1:
Operated (muting signal on)
SB 072
MUTING
B - SSNR
X - NO_1
X - NO_2
X - MS1
X - MS2
X - MP1
X - MP2
W - TS12
W - TPSy
W - TInt
W - TMut
W - TOPD
X - TOff
X - AuSt
X - SMd2
W - THlp
X - RSET
ENBL -
X
MAct
-
X
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license