1OUT:
Input for selecting whether both muting lamps are to be tested
simultaneously or alternately.
1OUT =1: Lamps are tested simultaneously. If positive-
switching outputs are used, output parameters
LMP1 and LMP2 can both be assigned the address
of a single output. Two optocouplers will need to be
connected to the PSS output.
If negative-switching outputs are used, two PSS
outputs will be needed.
1OUT= 0: Lamps are tested alternately. The output parameters
LMP1 and LMP2 must be assigned two different
addresses.
Output parameters
•
ENBL:
Enable flag bit
ENBL = 1: At least one filament is in order.
ENBL = 0: Fault detected: A defect has been found on both
filaments or on the optocouplers.
•
WARN:
Warning
WARN = 1: One of the two filaments is defective.
WARN = 0: Both filaments are in order.
•
LMP1:
Output for driving muting lamp 1 (Lamp 1)
LMP1 = 1: Muting lamp 1 on
LMP1 = 0: Muting lamp 1 off
•
LMP2:
Output for driving muting lamp 2 (Lamp 2)
LMP2 = 1: Muting lamp 2 on
LMP2 = 0: Muting lamp 2 off
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license