Safety guidelines – Pilz PSS SB HYD, Basic license User Manual
Page 161

Modular Block System: Hydraulic Presses
6-99
“Muting OFF”
The switch condition for “Muting OFF” is fulfilled when muting signals MP1
and MP2 are reactivated.
“Muting Start-Up”
Muting signals MP1 or MP2 must be operated if a vehicle is within the
range of the ESPE/AOPD.
Safety guidelines
WARNING!
The following information must be heeded!
Failure to comply with these guidelines could result in serious injury or
death.
• Refer to EN 61 496-1, 06/98 when setting parameters for SB072 and
when designing and operating the muting facility.
• Muting switches should be positioned so that it is impossible for a person
to trigger the muting function.
• The transport vehicle should be designed to make it impossible for
people to ride on it.
• Limit the size of the entry area by applying appropriate safety measures.
People must not be able to enter the danger area during the muting
phase.
• Consider the total duration of the muting phase if various transport
speeds are to be in operation.
• Remember that a new muting phase can only be introduced once the
previous phase has been completed.
• Maintenance gates should be provided if equipment is protected via a
muting signal.
Remember that the plant must be brought to a stop if the maintenance
gates are opened.
• Using muting signals provided by switch contacts
These contacts should use test pulses.
• Using sensors as muting signals MP1 and MP2
Pulsing is not possible when using sensors. For fault detection,
therefore, you should use a N/O contact as sensor MP1 and a N/C
contact as sensor MP2.
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license