Blocks required – Pilz PSS SB HYD, Basic license User Manual
Page 107

Modular Block System: Hydraulic Presses
6-45
Global parameters used in the administration data blocks
Global parameters may be set in OB120 using SB071.
• DW1002: Number of cycles for the reaction time of the feedback loop
with contactors
• DW1022: Minimum scan time
Blocks required
• DB015, DB016, DB017: Administration data blocks
The data blocks must consist of their total length of 1024 data
words and have READ/WRITE access (see Chapter 5, section
entitled “Administration data blocks...”).
• SB071:
Initialisation of global parameters in DB015, DB016 and DB017
This manual is related to the following products:
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license