Modular Block System: Hydraulic Presses
Standard Function Blocks
SB061: Emergency stop monitoring, category 4
Block header
Input parameters
•
SSNR:
Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).
•
EIN:
Reset button (N/O contact)
EIN = 0/1-pulse edge: Reset occurs
•
S1_Ö :
E-STOP N/C contact 1
•
S2_Ö :
E-STOP N/C contact 2
•
QAnf:
Automatic reset (PSS cold start)
QAnf = RLO-0 (M 110.00): No reset required.
Cycle: When the PSS is started up or cold started,
the enable is triggered without an additional reset.
QAnf = RLO-1 (M 110.01): Reset required.
Cycle: When the PSS is started up or cold
started, a reset is required through the input
parameter
EIN in order to trigger the enable.
•
QAut:
Automatic reset when E-STOP button is released
QAut = 0:
Reset through input parameter
EIN is required.
SB 061
NA_1
B - SSNR
X - EIN
X - S1_Ö
X - S2_Ö
X - QAnf
X - QAut
FG - X
SB061
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license