Modular Block System: Hydraulic Presses
6-81
Table for setting the global parameters:
INFORMATION
• All times must be entered in ms.
• The values suggested are default values. If working with these values
produces nuisance errors, you can determine which values would be
suitable as follows:
- Start from the default value
- Increase this value in stages until the nuisance errors stop.
Input
Parameters in
Limits
Suggested
parameters
Admin.-DB
in [ms]
values in [ms]
KoSy
DW 1001
0... 255
50
RRFK
DW 1002
0... 255
100
KU_S
DW 1003
0... 255
100
KU_R
DW 1004
0... 255
50
MaZy
DW 1005
0... 32 767
30 000, conforming
to EN 61 496-1
A.8.4/C.6.2
RBWS
DW 1006
0... 255
150, conforming
to EN 61 496-1
RVen
DW 1007
0... 32 767
None
DW 1008
DW 1009
Reserved
DW 1010
DW 1011
DW 1012
DW 1013
DW 1014
Reserved
DW 1015
DW 1016
DW 1017
DW 1018
DW 1019
Reserved
DW 1020
Reserved
DW 1021
Reserved
DW 1022
Min. scan time
DB002/DW0002
Reserved
DW 1023
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license