Block header, Input parameters, Standard function blocks – Pilz PSS SB HYD, Basic license User Manual

Page 120: Sb068

background image

6-58

Modular Block System: Hydraulic Presses

Standard Function Blocks

SB068: Monitoring ESPE / AOPDs with guarding and control function

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).
Value of DW (SSNR) = 0: No error found

NO_1:

N/O contact 1 of ESPE/AOPD
NO_1 = 0: Protected field broken
NO_1 = 1: Protected field clear

NO_2:

N/O contact 2 of ESPE/AOPD
NO_2 = 0: Protected field broken
NO_2 = 1: Protected field clear

OFF:

ESPE/AOPD in OFF mode
OFF = 1
GdO = 0

Guard function of ESPE/AOPD is deactivated.

SBrk = 0

The signal must come from a connected

DBrk = 0

operating mode selector switch block (SB51/52).

SB068

BWS_AOS

B - SSNR
X - NO_1
X - NO_2
X - OFF
X - GdO
X - SBrk
X - DBrk
X - RUN
X - CyRs
X - SSeq
X - ARSt
X - STyp
X - Test
X - RSET

ENBL -

X

TEST -

X

RdCy -

X

PWR

-

X

SB068