6-94

Modular Block System: Hydraulic Presses

Standard Function Blocks

SB072

INFORMATION
Important additional information on the use of sensors and contacts can
be found under “Safety guidelines” at the end of this SB description.

Switch conditions in sequential mode

“Muting ON”
Smd2 = 0: Muting signals MS1 and MS2 must be operated consecutively.

MS1 must then be released while MS2 remains operated.
The time between the operation of MS1 and MS2 must be at
least the length of one PSS cycle.
The time between the operation of MS1 and the release of
MS1 (while MS2 is operated) must be less than the value set
at input parameter

TS12.

The timer monitoring this time (input parameter

TS12) is

started by the 0/1-pulse edge at input parameter

MS1.

Smd2 = 1: Muting signals MS1 and MS2 must be operated consecutively.

The time between the operation of MS1 and MS2 must be at
least the length of one PSS cycle and less than the value set
at input paramter

TS12.

The timer monitoring this time (input parameter

TS12) is

started by the 0/1-pulse edge at input parameter

MS1.

Muting “OFF”
The suspension of the safety function is lifted as soon as:
- the ESPE/AOPD is released and
- the set interrupt time (input parameter

TInt) has elapsed

(the interrupt time is started when the ESPE/AOPD is released) or

- the ESPE/AOPD is released and

there are no more muting signals (i.e. MP1/MP2).

Muting “Start-Up”
MS2 or MP1 (or MP2, if present) must be operated if a vehicle is within the
range of the ESPE/AOPD.