• Monitoring the ESPE/AOPD outputs:

Feasibility check on signal 1 and signal 2 (input parameters

NO_1 and

NO_2), monitoring contact synchronisation time (DB 015/DW 1001).

• Reset pulse edge

Existing errors can be reset via a 0/1-pulse edge at the reset button
(input parameter

RSET).

• Function test:

A function test is carried out by breaking the protected field, clearing it
again and then pressing the reset button (input parameter

RSET). In the

case of hardware errors, a function test must always be carried out after
the error has been rectified.

• Start-up disabler:

A start-up disabler will be set if the PSS is switched on (PSS cold/warm
start), the SafetyBUS p I/O-Group is started (0/1 pulse edge at input
parameter

GRP) or if the guard function of the ESPE/AOPD is activated

(0/1 pulse-edge at the input parameter

GdOn).

The lifting of the disable will depend on the set start-up procedure. The
start-up sequence is established via the input parameter

SSeq (function

test or just reset in “guard only” mode).

• Reset lock:

A reset lock will be set if the protected field is interrupted during
operation. The lifting of the reset lock will depend on the set reset
procedure. The reset sequence is established via the input parameter
ARSt (automatic reset/press reset button).
In the case of hardware errors you will need to reset first and then carry
out a function test.

• Switching the ESPE/AOPD supply voltage:

The block has an output for switching the supply voltage to the ESPE/
AOPD (output parameter

PWR).

• Automatic Test of ESPE/AOPD

This block can be used to carry out an automatic function test (input
parameter

Test). A break in the protected field is simulated by switching

off the ESPE/AOPD emitter (output parameter

TEST). The maximum