Modular Block System: Hydraulic Presses
6-17
•
T1.2:
N/C button 1
•
T1.4:
N/O button 1
•
T2.2:
N/C button 2
•
T2.4:
N/O button 2
•
KU_S:
Contact switchover time between N/O and N/C contact on
pushbuttons
Permitted time range: 1 ... 1000 ms
Format: Constant fixed point number KF00001 … KF01000
Suggested value: KF00100
INFORMATION
If your plant does not run stably using the suggested value, you can
work out the value that suits your plant as follows:
- Select the suggested value as a starting point.
- Increase this value by appropriate time intervals until your plant runs
stably.
Please note:
Entering an excessively high time value for monitoring will reduce the
level of safety on your plant.
•
RSET:
Reset input
RSET = 0/1-signal edge: Trigger reset
WARNING!
The input parameter
Tipp is not intended for use on presses and therefore
must not be activated on presses.
On presses, this input should be assigned RLO-0 (M110.00).
•
Tipp:
Mode: “Jog mode using one button and setup speed”
Tipp = 0:
Mode: “Jog mode using one button” is blocked.
To disable jog mode using one button, the input
should be assigned RLO-0 (M110.00).
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license