6-8

Modular Block System: Hydraulic Presses

Standard Function Blocks

RSET:

Reset output
RSET = 1: The operating mode has been changed.

If the operating mode has been changed (e.g.
“reset ESPE/AOPD”), the

RSET output will be

high for one cycle.

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of DB015 (1st data block), until the fault has been fully dealt

with.

• Error messages in DB015

- Bit 00: Incorrect input signal

More than one input (

S1 ... S8) is high.

Remedy: Check switch, cable and input card, then reset
(input parameter

RSet)

- Bit 01: No input signal (

S1 ... S8) is high,

all inputs are low (cable break)
Remedy: Check switch, cable and input card, then reset
(input parameter

RSet)

- Bit 08: Switch changed when

LOCK = 1

Remedy:
If switch has not changed: Check switch, cable and input card,
then reset (input parameter

RSet)

If switch has changed: Check switch position and then reset
(input parameter

RSet)

- Bit 14:

RSet input constantly high or set too early
Remedy:
If

RSet input was not set too early and is constantly high:

Check switch, cable and input card, then reset
(input parameter

RSet)

If

RSet input was set too early: reset again

(input parameter

RSet)

INFORMATION
Error bits 00, 01 and 08 can only be reset in “Setup” mode.

SB051