Modular Block System: Hydraulic Presses

Standard Function Blocks

- Bit 03:

Fault as the signal changes at input parameter

ON,

feedback loop 2 (

FbL2) remains closed

Remedy: Check contactor, contacts, cable, input card, output
card, value of input parameter

TFbL and all conditions and

then reset (input parameter

RSET)

- Bit 04:

Fault during the static condition at input parameter

ON,

feedback loop 1 (

FbL1) interrupted

Remedy: Check contactor, contacts, cable, input card, output
card and all conditions and then reset (input parameter

RSET)

- Bit 05:

Fault during the static condition at input parameter

ON,

feedback loop 1 (

FbL1) closed

Remedy: Check contactor, contacts, cable, input card, output
card and all conditions and then reset (input parameter

RSET)

- Bit 06:

Fault during the static condition at input parameter

ON,

feedback loop 2 (

FbL2) interrupted

Remedy: Check contactor, contacts, cable, input card, output
card and all conditions and then reset (input parameter

RSET)

- Bit 07:

Fault during the static condition at input parameter

ON,

feedback loop 2 (

FbL2) closed

Remedy: Check contactor, contacts, cable, input card, output
card and all conditions and then reset (input parameter

RSET)

- Bit 08:

Reset input constantly 1 or set too early
Remedy: Release reset button and press again, otherwise:
check switch, cable and input card and reset again (input
parameter

RSET)

- Bit 09:

I/O-Group stop triggered while PSS is in normal RUN mode
Remedy: Start I/O-Group

• Error messages on the CPU-display

- E003: Administration data block has not been initialised

Remedy: Call SB071 in OB120

SB065