Blocks required – Pilz PSS SB HYD, Basic license User Manual
Page 129

Modular Block System: Hydraulic Presses
6-67
STyp = 0: Break the protected field, clear it and then press the
reset button (input parameter
RSET).
STyp = 1: Press the reset button (input parameter RSET),
break the protected field and then clear it.
- Bit 14:
More than one operating mode selected
Remedy: Check selector switch, cable, input card and all
conditions, then carry out a function test.
- Bit 15:
No operating mode selected
Remedy: Check selector switch, cable, input card and all
conditions, then carry out a function test
INFORMATION
Bits 10 ... 13 contain user information and cannot be released via the reset
button.
• Error messages on the CPU-display
- None
Global parameters used in administration data block DB015
Global parameters may be set in OB120 using SB070.
• DW1001: Cycles for contact synchronisation time N/O / N/O
• DW1005: Cycles for time for cycling ESPE/AOPD
• DW1006: Cycles for ESPE/AOPD reaction time
Blocks required
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.
• SB070
Initialisation of global parameters in DB015
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license