Blocks required – Pilz PSS SB HYD, Basic license User Manual

Page 129

background image

Modular Block System: Hydraulic Presses

6-67

STyp = 0: Break the protected field, clear it and then press the

reset button (input parameter

RSET).

STyp = 1: Press the reset button (input parameter RSET),

break the protected field and then clear it.

- Bit 14:

More than one operating mode selected
Remedy: Check selector switch, cable, input card and all
conditions, then carry out a function test.

- Bit 15:

No operating mode selected
Remedy: Check selector switch, cable, input card and all
conditions, then carry out a function test

INFORMATION
Bits 10 ... 13 contain user information and cannot be released via the reset
button.

• Error messages on the CPU-display

- None

Global parameters used in administration data block DB015

Global parameters may be set in OB120 using SB070.
• DW1001: Cycles for contact synchronisation time N/O / N/O

• DW1005: Cycles for time for cycling ESPE/AOPD

• DW1006: Cycles for ESPE/AOPD reaction time

Blocks required

• DB015:

Administration data block

DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.

• SB070

Initialisation of global parameters in DB015