Sb092: enable switch, Block header, Input parameters – Pilz PSS SB HYD, Basic license User Manual

Page 220: Standard function blocks sb092

background image

6-158

Modular Block System: Hydraulic Presses

Standard Function Blocks

SB092

SB092: Enable switch

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).
Value of DW (SSNR) = 0: no error found

ON:

Switch operating mode on/off (enable function)
ON = 0: Operating mode switched off
ON = 0/1 pulse edge: Switch on operating mode

NC:

N/C contact
(please refer to “Switching diagrams”).

NO:

N/O contact
(please refer to “Switching diagrams”).

INFORMATION
Both contacts

NC and NO should be provided with different

test pulse outputs (test pulses).

AuSt:

Automatic start/start-up lock when the PSS starts up
AuSt = 0:

Start-up disabled when PSS starts up
When the PSS starts up, a reset via the input
parameter

RSET is required. To set the start-up

lock on the SB, the input parameter should be
assigned RLO-0 (M 110.00).

SB 092

ENBL_DEV

B - SSNR
X - ON
X - NC
X - NO
X - AuSt
X - ARst
X - RSET

ENBL - X