Intended Use

Modular Block System: Hydraulic Presses

SB067: Feedback loop monitoring

SB067 is a standard function block for the direct control and monitoring of
contactors up to category 4, in accordance with EN 954-1, 03/97.

Features and application areas:

• Feedback loop is monitored during the change in the enable flag and

while the contactor is in a static condition

• Feedback loop can be monitored on two separate feedback loops of

main contactors connected in series

• Feedback loop can be monitored on group contactors

INFORMATION
Input circuitry:

• To achieve category 4, two independent shutdown routes must be

provided within the current path of the potentially dangerous drive

• If wiring is to be laid outside the control cabinet, feedback loops must use

test pulses.

• Feedback loops must use test pulses if the possibility of a short-circuit

cannot be excluded.

• If only one contactor is used to switch a potentially dangerous drive, it

must be possible to switch this off via a group contactor within the
current path (selective shutdown).

• The group contactor must also be monitored through a feedback loop.