Error messages – Pilz PSS SB HYD, Basic license User Manual
Page 105

Modular Block System: Hydraulic Presses
6-43
The acknowledgements
FbL1 and FbL2 are also monitored in the static
condition. If there are discrepancies between the set and true condition, an
error message will be issued (
ENBL = 0) and the contactors will be
switched off immediately (
K1 = 0 and K2 = 0). The error will need to be
reset.
It is possible to reset errors via the input parameter
RSET both when ON =
0 and when
ON = 1. However, a prerequisite for setting the enable and,
when
ON = 1, switching on the contactors, is that the signals from the
feedback loops are correct.
Error messages
Any fault that is detected will be stored in the corresponding error data
word (
SSNR) of the administration data block (1st data block), until the
fault has been fully dealt with.
• Error messages in the administration data block
- Bit 00:
Fault as the signal changes at input parameter
ON,
feedback loop 1 (
FbL1) remains open
Remedy: Check contactor, contacts, cable, input card, output
card, value of input parameter
TFbL and all conditions and
then reset (input parameter
RSET)
- Bit 01:
Fault as the signal changes at input parameter
ON,
feedback loop 1 (
FbL1) remains closed
Remedy: Check contactor, contacts, cable, input card, output
card, value of input parameter
TFbL and all conditions and
then reset (input parameter
RSET)
- Bit 02:
Fault as the signal changes at input parameter
ON,
feedback loop 2 (
FbL2) remains open
Remedy: Check contactor, contacts, cable, input card, output
card, value of input parameter
TFbL and all conditions and
then reset (input parameter
RSET)
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license