Examples – Pilz PSS SB HYD, Basic license User Manual
Page 260

8-24
Examples
Modular Block System: Hydraulic Presses
Safety gate monitoring with manual start and manual restart,
category 4
Block used: SB064/S_GATE
Cyclical function test on the gate:
The following application does not require a cyclical function test on the
gate.
However, should you wish to use this function, you should assign the
“Machine running” signal to the input parameter
MEin.
Set operating mode:
The following operating mode is set for this application:
ARSt = 0: Reset lock activated (manual restart)
The operator must reset each time the safety gate opens
(input parameter
Strt).
NFkT = 1
No function test on safety gate when PSS starts up/resets
AuSt = 0
Start up disabler activated (manual start)
The operator must reset each time the PSS is started up or
resets (input parameter
Strt).
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license