Blocks required – Pilz PSS SB HYD, Basic license User Manual
Page 101

Modular Block System: Hydraulic Presses
6-39
- Bit 12:
Gate closed, S1 was not open
Remedy: Open gate, check switch, cable and input card and
then carry out function test and reset (input parameter
RSET)
- Bit 13:
Gate closed, S2 was not open
Remedy: Open gate, check switch, cable and input card, carry
out a function test and then reset (input parameter
RSET)
- Bit 14:
RSET input constantly high or set too early
Remedy: If
RSET input was not set too early and is constantly
high: Check switch, cable and input card, then reset (input
parameter
RSET).
If
RSET input was set too early: reset again
(input parameter
RSET)
- Bit 15:
Gate closed,
RSET signal is missing
Remedy: Check all conditions and then reset
(input parameter
RSET)
• Error messages on the CPU-display
- E003
Administration data block has not been initialised
Remedy: Call SB071 in OB120
Global parameters used in the administration data blocks
The global parameter may be set in OB120 using SB071.
• DW1022: Minimum scan time
Blocks required
• DB015, DB016, DB017: Administration data blocks
The data blocks must consist of their total length of 1024 data
words and have READ/WRITE access (see Chapter 5, section
entitled “Administration data blocks...”).
• SB071:
Initialisation of global parameters in DB015, DB016 and DB017
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license