Edwards Signaling eFSA250 User Manual
Page 89

Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
77
Device option Description
Input module device types
Note:
Available device types depend on the position of the slide switch on
the front of the module. For example, if the slide switch is in the alarm
position, only alarm device types are available. Device type selection may
affect the panel state that is initiated when the device is active, the default
contact ID is transmitted, and other panel responses for the devices of
normal conditions.
2Wire Class A: Allows for the monitoring of compatible two-wire conventional
smoke detectors in a Class A circuit (that do not require alarm verification)
and normally open contact initiating devices on the same circuit.
2Wire Class B: Allows for the monitoring of compatible two-wire conventional
smoke detectors in a Class B circuit (that do not require alarm verification)
and normally open contact initiating devices on the same circuit
2Wire verify Class A: Allows for the monitoring of compatible two-wire
conventional smoke detectors in a Class A circuit (that require alarm
verification)
2Wire verify Class B: Allows for the monitoring of compatible two-wire
conventional smoke detectors in a Class B circuit (that require alarm
verification)
Alarm: For four-wire smoke detectors and contact devices. All activations are
immediately considered as alarms. Circuit cannot be restored until devices
are restored to normal and the panel is reset.
Duct alarm: For four-wire conventional duct smoke detectors. All activations
are immediately considered as alarms. Circuit cannot be restored until
devices are restored to normal and the panel is reset.
Heat: For heat detectors and contact devices. All activations are immediately
considered as alarms. Circuit cannot be restored until devices are restored
to normal and the panel is reset.
Pull station: For pull station devices. All activations are immediately
considered as alarms.
Remote drill: For a remote switch that when activated, starts the panel’s drill
operation.
Remote reset: For a remote switch that when activated, resets the panel.
Remote signal silence: For a remote switch that when activated, silences the
signaling devices.
Waterflow: For connecting vane type and pressure flow switches. Activations
are considered as alarms. A 16-second alarm delay applies to waterflow
activations. NACs activated by the waterflow device type cannot be silenced
until the panel is reset. Waterflow activations do not invoke in-suite signal
silence.