Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
133
5. Choose Correlation Groups and enter the number
of the correlation group.
6. Press Enter to toggle between possible values:
To add the event to the group, choose Included.
— or —
To remove it from the group, choose Excluded.
7. Repeat steps 7 to 9 to add or remove the event
from any remaining correlation groups to be
configured.
8. Choose Save.
9. Choose Event Notification.
10. Choose Active.
11. Configure active event notification. (Not all the
options shown here are displayed on all systems.)
Printer: This controls whether event information is
sent to the printer. Press Enter to toggle between
Yes and No.
Coder: Four-digit coded output that is played in
response to alarm conditions (00-00-00-00 to 99-
99-99-99).
Dialer options are listed below.
• Acct 1 & 2: Event information is sent to both
dialer accounts
• Acct 1: Event information is sent to dialer
account one
• Acct 2: Event information is sent to dialer
account two
• None: Event information is not sent to the
dialer.
CID: Contact ID event code (000 to 999).
NET (1-8): Yes or No. This controls whether event
information is sent to the connected network.
12. When you have finished, choose Save.
13. Press the Menu button to exit menu mode, or
continue programming.
Correlation Groups
Event Notification
Correlation Groups
Group 001
Status Included
Enter Exit
Unconfigured Alarm
Correlation Groups
Event Notification
Event Notification
Active
Active
Printer Yes<>
Code 10-10-10-10
Dialer Account 1&2
CID 110
NET(1-8) Yes
_Save