Programming in-suite signal silence – Edwards Signaling eFSA250 User Manual
Page 104

Chapter 2: Front panel programming
92
E-FSA64 and E-FSA250 Technical Reference Manual
Yes to add a panel event
No to remove a panel event
7. Choose Save.
Add/Remove Device
Add/Rem Panel Event
Add/Rem Panel Event
Reset Activate No<>
Reset Restore No<>
Signal Silence No<>
Programming in-suite signal silence
In-suite signal silence is programmed using two separate menus:
• Configure the elapse timer for in-suite signal silence by displaying the
Program > Advanced Program > Panel Operation menu.
• The function is enabled for individual correlation groups through the
Program > Advanced Program > Loop Configuration > Correlation Groups
menu.
This section provides instructions for setting both in-suite signal silence options.
Note:
When setting up correlation groups for in-suite signal silence, the group’s
activation count must be set to 1. See “Setting a correlation group’s activation
count” on page 88.
To enable in-suite signal silence for a correlation group:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3 Choose Loop Configuration.
4. Choose Correlation Groups and enter the number
of the correlation group. (Values range from 001 to
199.)
5. Choose Suite Sig Sil.
6. Select:
Yes to enable in-suite signal silence.
No to disable it.
7. Choose Save.
Advanced Program
Loop Configuration
Loop Configuration
Loop Class
Zone
Correlation Groups
Correlation Groups
Number 001<>
Correlation Group 001
Add/Remove Zone
Add/Remove NAC
Add/Remove Device
Suite Sig Sil YES<>
Correlation Group 001
Copy 001
Remove All
Save