Chapter 2: Front panel programming
76
E-FSA64 and E-FSA250 Technical Reference Manual
Device option Description
Photoelectric smoke detectors
Smoke: For smoke detectors and contact devices. All activations are
immediately considered as alarms. Circuit cannot be restored until devices
are restored to normal and the panel is reset.
Smoke verified: For smoke detectors and contact devices. Two-wire smoke
detector activations are verified (delayed and confirmed) before activating an
alarm. Four-wire smoke detectors and contact devices are not verified and
immediately considered as alarms. Circuit cannot be restored until devices
are restored to normal and the panel is reset.
Supervisory latching: For detectors that trigger an active (supervisory) event.
Detectors with this device type remain active until the condition that
activated them is restored and the control panel is reset.
Supervisory nonlatching: For detectors that trigger an active (supervisory)
event. Detectors with this device type remain active until the condition that
activated them is restored. Resetting the control panel is not required.
Duct detectors
Duct alarm: For duct smoke detectors. All activations are immediately
considered as alarms. Circuit cannot be restored until devices are restored
to normal and the panel is reset.
Duct supervisory latching: Detectors with this device type when activated
immediately places the panel in the supervisory state, turns on supervisory
LEDs, and activates the supervisory relays. The detectors remain active until
the smoke condition clears and the panel is reset.
Duct supervisory nonlatching: Detectors with this device type when activated
immediately places the panel in the supervisory state, turns on supervisory
LEDs, and activates the supervisory relays. The detectors remain active until
the smoke condition clears. Resetting the panel is not required.
Heat detectors
Heat alarm: For heat detectors and contact devices. All activations are
immediately considered as alarms. Circuit cannot be restored until devices
are restored to normal and the panel is reset.
Heat alarm RoR: For heat detectors and contact devices with rate-of-rise. All
activations are immediately considered as alarms. Circuit cannot be restored
until devices are restored to normal and the panel is reset.