Edwards Signaling Genesis Ceiling Speaker-Strobe User Manual
Genesis ceiling speaker-strobe installation sheet, Description, Installation
© 2013 UTC Fire & Security. All rights reserved.
1 / 4
P/N 3100614 • REV 07 • REB 30JAN13
Genesis Ceiling Speaker-Strobe
Installation Sheet
Description
The Genesis Ceiling Speaker-Strobe is a fire alarm notification
appliance designed for indoor ceilings and walls. See Table 1
for a list of model numbers.
Table 1: Models
Description
Number
Speaker-strobe,
25 VRMS, 15 to 95 multi-cd,
white
ADTGC-S2VM
MGC-S2VM
EGC-S2VM
XLSGC-S2VM
GC-S2VM
ZGC-S2VM
Speaker-strobe,
25 VRMS, 15 to 95 multi-cd,
white, with FIRE marking
ADTGCF-S2VM
MGCF-S2VM
EGCF-S2VM
XLSGCF-S2VM
GCF-S2VM
ZGCF-S2VM
Speaker-strobe,
70 VRMS, 15 to 95 multi-cd,
white
ADTGC-S7VM
MGC-S7VM
EGC-S7VM
XLSGC-S7VM
GC-S7VM
ZGC-S7VM
Speaker-strobe,
70 VRMS, 15 to 95 multi-cd,
white, with FIRE marking
ADTGCF-S7VM
MGCF-S7VM
EGCF-S7VM
XLSGCF-S7VM
GCF-S7VM
ZGCF-S7VM
Speaker-strobe,
70 VRMS, 15 to 95 multi-cd,
red, with FIRE marking
EGCFR-S7VM
GCFR-S7VM
MGCFR-S7VM
The speaker-strobe includes field configurable switches for
selecting the desired candela output and wattage tap. These
settings lock in place and remain visible after final installation.
This strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971 Signaling
Devices for the Hearing Impaired and the latest Canadian
standard CAN/ULC-S526. Synchronized operation requires a
separately installed synchronization control module. See
Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements
in the latest editions of the NFPA codes and standards and
Canadian Electrical Code, Part 1, Section 32 and CAN/ULC-
S524, Standard for the Installation of Fire Alarm Systems, and
in accordance with the local authorities having jurisdiction.
Table 2: Compatible synchronization module models
Description
Number
Auto-sync output module
SIGA-CC1S
SIGA-MCC1S
GSA-CC1S
GSA-MCC1S
Genesis signal master -
remote mount
ADTG1M-RM
MG1M-RM
EG1M-RM
XLSG1M-RM
G1M-RM
ZG1M-RM
Installation
WARNING:
To reduce the risk of shock, disconnect all power
and allow 10 minutes for stored energy to dissipate before
handling.
Caution:
Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field
wires around the terminals.
Note
: When installed, these devices are not centered on the
electrical box. Make sure boxes are mounted to compensate
for this difference. See Figure 7.
To install the speaker-strobe:
1. Open the cover by depressing the tab on the side of the
unit with a small screwdriver. Hinge the cover down, to
access the mounting screws and selectable candela and
wattage switches. The cover is also detachable for
installation convenience.
2. If temporal strobe (private mode) operation is desired, cut
jumper JP1. See Figure 2.
3. Connect the speaker and strobe terminals to the signal
circuit field wiring. For the unit to function properly,
observe polarity. See Figure 4.
4. Slide the candela switch to the desired candela output (15,
30, 75, or 95 cd) by aligning it with the indicator below the
switch. See Figure 1.
5. Slide the wattage switch to the desired wattage tap (2 W,
1 W, 1/2 W, or 1/4 W) by aligning it with the indicator
below the switch. See Figure 1.
6. Mount the unit onto a compatible electrical box. See