Sa-cla wiring – Edwards Signaling eFSA250 User Manual
Page 35

Chapter 1: Installation and wiring
E-FSA64 and E-FSA250 Technical Reference Manual
23
Figure 31: Computer download wiring
RS-232 cable
DB-9 female
Computer
DB-9 COM port
on back of computer
To RS-232 card
Figure 32: Pin designations on female DB-9 plug (back view)
Pin 2 RXD
Pin 3 TXD
Pin 5 COM
Table 6: SA-232 card to computer DB-9 connections
SA-232 card
DB-9
Description [1]
GND
COM (pin 5)
Black wire (ground connection)
RTS
-
Not used
TXD
RXD (pin 2)
White wire (communication)
RXD
TXD (pin 3)
Red wire (communication)
[1] Wire colors refer to Model 260097 RS-232 Cable
SA-CLA wiring
The SA-CLA card is used to supply wiring for Class A NACs and redundant
Class B remote annunciator circuits on eFSA64 control panels.
Circuit specifications
• Operating current
Standby: 3 mA
Alarm: 60 mA max.
• Max. resistance: 26 Ω
• Max. capacitance: 0.35 µF
• Max. current: 2.5 A per circuit