Net options, Auto programming procedure – Edwards Signaling eFSA250 User Manual
Page 78

Chapter 2: Front panel programming
66
E-FSA64 and E-FSA250 Technical Reference Manual
NET options
Table 22 describes the network options used to set up the Ethernet card.
Table 22: Auto programming — NET options
Option
Description
Account ID Enter the six-digit code for the central monitoring
station (CMS) account.
Network
Account ID 676968
IP 000.000.000.000
Event Notif. Event>
Network
Receiver# 000
Line# 000
Save
IP
Enter the IP address for the CMS.
Event
notification
Set event notification (event reporting) to:
Device: Only device information is reported or
transmitted, no zone information. This setting uses
default device event notification settings for
reporting events. See “Factory default settings” on
page 36.
Zone:
When a device is a member of a zone, only
the zone information is reported or transmitted, no
device information. This setting uses default zone
event notification settings for reporting events. See
“Factory default settings” on page 36.
Event:
Only the event type (alarm, supervisory,
trouble, etc.) is reported or transmitted, no device
or zone information. This setting uses the default
CMS event notification settings for reporting
events. See “Factory default settings” on page 36.
Receiver
number
Enter the CMS receiver number. Specifies the
CMS receiver number to be displayed in the
message sent to the receiver. This number is user-
defined.
Line
number
Enter the CMS receiver line number. Specifies the
receiver’s line number to be displayed in the
message sent to the receiver. This number is user-
defined.
Auto programming procedure
Use the following procedure to auto program the panel, referring to the options
listed in Table 20 on page 62. Not all options shown are displayed on all
systems.
To auto program a panel:
1. Press the menu button and choose Program.
2. Choose Auto Program.
Main Menu
Reports
Test