Changing the passwords, Restoring the factory default settings – Edwards Signaling eFSA250 User Manual
Page 63

Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
51
Changing the passwords
The second step in programming the panel is to change the level one, level two,
and remote annunciator passwords.
Notes
• We recommend that you change the default passwords before programming
the system.
• The system automatically logs you off after four minutes of inactivity.
To change the passwords:
1. Press the Menu button and choose Program.
2. Choose Password.
3. Enter a level two password.
4. Select the password to be changed: Level 1, Level
2, or Remote (Ann.).
5. Enter the old password and press Enter.
6. Enter the new password and press Enter.
7. Repeat steps 4 through 6 for each password to be
changed.
8. Press the Menu button to exit menu mode, or
continue programming.
Main Menu
Reports
Test
Control
Program
Program
Date and Time
Clear History
Password
Enter Password
0000
Password
Level 1
Level 2
Remote (Ann.)
Enter Old Password
0000
Enter New Password
0000
Restoring the factory default settings
Use the Restore Defaults command to overwrite most custom settings in the
panel, the dialer (CMS network), or both. This lets you commission the panel as
a common alarm system, or remove custom settings in preparation for advanced
programming.