Edwards Signaling eFSA250 User Manual
Page 138

Chapter 2: Front panel programming
126
E-FSA64 and E-FSA250 Technical Reference Manual
Option
Description
Zone resound
Set zone resound to:
On: NACs resound each time a device in the zone goes into
alarm even if they were silenced.
Off: Inhibits the NACs from turning on again (after they were
silenced) when a second device in the zone goes into alarm.
The “off” setting is not acceptable for UL/ULC installations. See
“UL 864 programming requirements” for details.
Reset inhibit
Set the time to:
Off: Panel reset is operational immediately after NACs turn on.
1 minute: Panel reset is operational one minute after NACs turn
on.
Auto signal silence
Set auto signal silence to:
Off: Does not allow the panel to automatically silence the
signals.
5 to 30 minutes: Allows the panel to automatically silence the
signals after the selected time period expires.
Suite signal silence
Set the timer duration. The range of possible values is 1 to 10
minutes. The default value is 10 minutes.
Daytime start
Set the start time for daytime sensitivity.
Nightime start
Set the start time for nighttime sensitivity.
Date
Set the date format to:
U.S.: MM/DD/YYYY
Canada: DD/MM/YYYY
LCD banner
Enter the desired banner text for line one and line two using the
keypad. Each line can have up to 20 characters. When you
have finished, choose Save. The LCD banner does not display
when the panel is in any off-normal state.
Aux power reset
On: “Reset” temporarily turns off the resettable aux power
output. This is required when the output is used for powering
four-wire smoke or four-wire duct smoke detectors.
Off: “Reset” does not turn off the resettable aux power output.
This is required when the output is used to power remote
annunciators.
Event notification
Set event notification to:
Zone: When a device is a member of a zone, only the zone
information is sent to the LCD, LEDs, printer, and dialer. Note,
device level reporting configuration is not available.
Zone/device: Zone information is sent to the LCD and LEDs.
Device information is sent to the printer and dialer. Zone/device
reporting locations can be configured through custom