Edwards Signaling Genesis Temporal Horn-Strobe User Manual
Genesis temporal horn-strobe installation sheet, Description, Installation
© 2010 UTC Fire & Security. All rights reserved.
1 / 4
P/N 3100560 • REV 5.0 • ISS 25AUG10
Genesis Temporal Horn-Strobe Installation
Sheet
Description
The Genesis Temporal Horn-Strobe is a fire alarm notification
appliance designed for indoor walls. See Table 1 for a list of
model numbers.
Table 1: Models
Description
Number
Horn-strobe,
15 to 110 multi-cd,
white
ADTG1-HDVM
EG1-HDVM
G1-HDVM
MG1-HDVM
XLSG1-HDVM
ZG1-HDVM
Horn-strobe,
15 to 110 multi-cd,
white, with FIRE marking
ADTG1F-HDVM
EG1F-HDVM
G1F-HDVM
MG1F-HDVM
XLSG1F-HDVM
ZG1F-HDVM
Horn-strobe,
15 to 110 multi-cd,
red
ADTG1R-HDVM
EG1R-HDVM
G1R-HDVM
MG1R-HDVM
XLSG1R-HDVM
ZG1R-HDVM
Horn-strobe,
15 to 110 multi-cd,
red, with FIRE marking
ADTG1RF-HDVM
EG1RF-HDVM
G1RF-HDVM
MG1RF-HDVM
XLSG1RF-HDVM
ZG1RF-HDVM
Trim plate,
white
ADTG1T
EG1T
G1T
MG1T
XLSG1T
ZG1T
Trim plate,
white, with FIRE marking
ADTG1T-FIRE
EG1T-FIRE
G1T-FIRE
MG1T-FIRE
XLSG1T-FIRE
ZG1T-FIRE
Description
Number
Trim plate,
red
ADTG1RT
EG1RG
1RT
MG1RT
XLSG1RT
ZG1RT
Trim plate,
red, with FIRE marking
ADTG1RT-FIRE
EG1RT-FIRE
G1RT-FIRE
MG1RT-FIRE
XLSG1RT-FIRE
ZG1RT-FIRE
There are field-configurable options for selecting dB output,
horn signal, or strobe signal output. See Figure 1.
The strobe includes a field-configurable switch for selecting the
desired candela output. The candela output setting is locked in
place and remains visible after final installation. See Figure 2.
This strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971
Signaling
Devices for the Hearing Impaired and the latest Canadian
standard CAN/ULC-S526. Synchronized operation requires a
separately installed synchronization control module. See
Table 2 for a list of compatible synchronization modules.
Table 2: Compatible synchronization module models [1]
Description
Number
Genesis Signal Master
Snap-on Mount
EG1M
ADTG1M
MG1M
XLSG1M
G1M
ZG1M
Genesis Signal Master -
Remote Mount
EG1M-RM MG1M-RM
G1M-RM
Auto-Sync Output Module SIGA-CC1S SIGA-MCC1S
Dual Input Signal Module
SIGA-CC2A SIGA-MCC2 A
Auxiliary Power Supply
APS6A
APS10A
Power Supply
BPS6A
BPS10A
[1] Synchronization module requirements are determined by the
application.
Installation
Install this device in accordance with applicable requirements
in the latest editions of the NFPA codes and standards; the
National Building Code of Canada; the Canadian Electrical
Code, Part 1, Section 32, and in accordance with the local
authorities having jurisdiction.