Panel programming – Edwards Signaling eFSA250 User Manual
Page 121

Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
109
Printer: Yes or No. This controls whether event information is
sent to the printer
Dialer:
• Acct 1 2: Event information is sent to both dialer accounts
• Acct 1: Event information is sent to dialer account one
• Acct 2: Event information is sent to dialer account two
• None: Event information is not sent to the dialer
NET: Yes or No. Controls whether event information is sent to
the connected network
CID: Contact ID event code (000 to 999)
To program a zone:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3. Choose Loop Configuration.
4. Choose Zone and enter the zone number.
5. Program each zone in the system using Table 29
on page 108.
6. When you finish programming an option, choose
Save, and then continue.
7. Press the Menu button to exit menu mode, or
continue programming.
Loop Configuration
Loop Class
Zone
Correlation Groups
Zone
Number 01>
Zone 01
Zone 01
Type Alarm<>
Label >
Correlation Groups
Zone 01
Correlation Groups
Event Notification
Save
Panel programming
The panel options to be configured include:
• NAC circuits (“NACs”)
• Annunciator class
• Annunciator
• Dialer and network (“CMS device”)
• Printer
• IP address (“IP”)
• Subnet mask (“MSK”)
• Gateway (“GWY”)
Most options have a factory default setting that you can accept or change. See
“Factory default settings” on page 36.