Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
113
3. Enter the NAC (number) you want to program, and
then press Enter.
Note:
NAC 3 and 4 are not available if either NAC
1 or 2 or both are set to Class A.
4. Program each NAC in the system using Table 30
on page 110.
5. When you finish programming each option,
choose Save.
6. Press the Menu button to exit menu mode, or
continue programming.
Annunciator
Panel NAC
NAC 1<>
Panel NAC 1
Class Class A<>
Type Cont. Non Sil<>
Label >
Panel NAC 1
Correlation Groups
Event Notification
Save
Setting annunciator classes
Program the annunciators’s wiring class (Class A or Class B). You must install
the optional SA-CLA module if you have class annunciator wiring on the 64 point
panel.
Default: Class B
To set the annunciator class:
1. Display the panel configuration options menu. See
“Panel programming” on page 109.
2. Choose Ann. Class.
3. Select either Class A or Class B.
4. Program other panel configuration options or
choose Save if you’re finished.
5. Press the Menu button to exit menu mode, or
continue programming.
Panel Configuration
Panel NAC
Ann. Class A<>
Annunciator
Panel Configuration
Ann. Class A<>
Annunciator
Save
Annunciator programming
Each annunciator on the annunciator loop must be programmed for type, number
of expanders, label, and event notification. Up to eight annunciators can be
connected on the loop and each must be programmed separately. You must also
set the address on each annunciator by using the DIP switch on the back of the
annunciator.