Edwards Signaling 125 Class Incand User Manual
Description, Electrical specifications, Mechanical specifications
Installation Instructions for 125 Class Beacons,
INCANDESCENT Models
Description
Edwards 125 Class Beacons are UL and cUL listed signaling
appliances rated for NEMA 4X applications. Two versions
of incandescent beacons are available: Flashing (125INC
F)
and Steady-on (125INC
S). Both types can be either surface
or conduit mounted.
A protective wire guard, Cat. No. 125GRD, is available.
Electrical Specifications
GRAY BASE
BLACK BASE
Catalog Number Catalog Number
Voltage
Current
Flashing Incandescent
125INCF*24D
125INCF*24DB
24V DC
0.610A
125INCF*120A
125INCF*120AB
120V AC 50/60 Hz
0.510A
Steady-On Incandescent
125INCS*24D
125INCS*24DB
24V DC
0.610A
125INCS*120A
125INCS*120AB
120V AC 50/60 Hz
0.510A
*Letter in this position designates lens color:
A - amber, B - blue, C - clear, G - green, or R - red
Mechanical Specifications
Outdoor Locations
Temperature Ratings ........... -31F to +150F (-35C to +66C)
Installation
WARNING
To prevent electrical shock, ensure that
power is turned off before installing the
signal.
Conduit Mounting (Figure 1)
1. Thread the 18" (45.7 cm) signal wire leads through 1/2"
conduit into an approved conduit outlet box.
2. Thread the conduit onto the base of the signal.
3. Using wire nuts (not supplied), connect the signal's wire
leads as shown in Figure 1. Polarity must be observed
for DC models. For AC models, polarity is not important.
Panel Mounting (Figure 2)
Note: When panel mounting the beacon, the surface and
construction details of the panel must be taken into
consideration in order to ensure that the integrity
of the outdoor, NEMA 4X rating is fully maintained.
Installer should evaluate.
1. Place the mounting gasket (supplied) over the hole in
the panel and route the signal wires through the gasket
and the hole in the panel.
2. Insert the base through the hole in the panel and screw
the locking nut (supplied), with the raised locking edge
facing the mounting surface, onto the base to secure the
beacon.
3. Using wire nuts (not supplied), connect the signal's wire
leads as shown in Figure 2. Polarity must be observed.
Maintenance
WARNINGS
To prevent electrical shock, ensure
power is turned off before installation or
maintenance.
To avoid risk of injury, install lens before
energizing.
Cleaning
To maintain optimum light visibility, the exterior lens surfaces
should be periodically cleaned with a soft clean cloth us-
ing water and a mild detergent. Disconnect power before
cleaning.
Light Source Replacement
1. Conduit Mounted Modules: Disconnect wiring and, if
necessary, unscrew base from conduit (Figure 1).
Panel Mounted Modules: Disconnect wiring and
remove locking nut that secures the base to the panel
(Figure 2).
2. Remove screws that secure the lens to the base from
bottom of base and remove lens.
3. Unplug lamp and replace with appropriate new lamp (as
specified in Table 1 - Replacement Parts). Reattach lens
to base and fasten with screws removed in step 2.
P/N 3101757 ISSUE 3
© 2010
http://www.edwardssignaling.com Phone: (800) 336-4206 Fax: (800) 454-2363