Installation Instructions for 125 Class Beacons,

INCANDESCENT Models

Description

Edwards 125 Class Beacons are UL and cUL listed signaling

appliances rated for NEMA 4X applications. Two versions

of incandescent beacons are available: Flashing (125INC

F)

and Steady-on (125INC

S). Both types can be either surface

or conduit mounted.
A protective wire guard, Cat. No. 125GRD, is available.

Electrical Specifications

GRAY BASE

BLACK BASE

Catalog Number Catalog Number

Voltage

Current

Flashing Incandescent

125INCF*24D

125INCF*24DB

24V DC

0.610A

125INCF*120A

125INCF*120AB

120V AC 50/60 Hz

0.510A

Steady-On Incandescent

125INCS*24D

125INCS*24DB

24V DC

0.610A

125INCS*120A

125INCS*120AB

120V AC 50/60 Hz

0.510A

*Letter in this position designates lens color:

A - amber, B - blue, C - clear, G - green, or R - red

Mechanical Specifications

Outdoor Locations

Temperature Ratings ........... -31F to +150F (-35C to +66C)

Installation

WARNING

To prevent electrical shock, ensure that

power is turned off before installing the

signal.

Conduit Mounting (Figure 1)
1. Thread the 18" (45.7 cm) signal wire leads through 1/2"

conduit into an approved conduit outlet box.

2. Thread the conduit onto the base of the signal.
3. Using wire nuts (not supplied), connect the signal's wire

leads as shown in Figure 1. Polarity must be observed

for DC models. For AC models, polarity is not important.

Panel Mounting (Figure 2)
Note:
When panel mounting the beacon, the surface and

construction details of the panel must be taken into

consideration in order to ensure that the integrity

of the outdoor, NEMA 4X rating is fully maintained.

Installer should evaluate.

1. Place the mounting gasket (supplied) over the hole in

the panel and route the signal wires through the gasket

and the hole in the panel.

2. Insert the base through the hole in the panel and screw

the locking nut (supplied), with the raised locking edge

facing the mounting surface, onto the base to secure the

beacon.

3. Using wire nuts (not supplied), connect the signal's wire

leads as shown in Figure 2. Polarity must be observed.

Maintenance

WARNINGS

To prevent electrical shock, ensure

power is turned off before installation or

maintenance.
To avoid risk of injury, install lens before

energizing.

Cleaning
To maintain optimum light visibility, the exterior lens surfaces

should be periodically cleaned with a soft clean cloth us-

ing water and a mild detergent. Disconnect power before

cleaning.
Light Source Replacement
1. Conduit Mounted Modules: Disconnect wiring and, if

necessary, unscrew base from conduit (Figure 1).

Panel Mounted Modules: Disconnect wiring and

remove locking nut that secures the base to the panel

(Figure 2).

2. Remove screws that secure the lens to the base from

bottom of base and remove lens.

3. Unplug lamp and replace with appropriate new lamp (as

specified in Table 1 - Replacement Parts). Reattach lens

to base and fasten with screws removed in step 2.

P/N 3101757 ISSUE 3