Chapter 2: Front panel programming
120
E-FSA64 and E-FSA250 Technical Reference Manual
6. Press the Menu button to exit menu mode, or
continue programming.
Dialer
Type Single Line>
Account 1
Account 2
CMS Device
Swngr Shtdn Rp.200<>
Event Notification
Save
CMS network (transmitter) programming
The information programmed here pertains to the central monitoring station
(CMS) network that the control panel uses to communicate with the CMS. This is
a TCP/IP Ethernet network. Event information is sent to the CMS just as it is
when using a dialer; however, the transmission is over an Ethernet network
rather than the telephone lines.
To program the panel for network reporting, you must install and enable the
optional SA-ETH Ethernet module. Once installed, program only the network
card connected to a compatible network receiver, as listed in the appropriate
compatibility guide.
Obtain the following information from the central monitoring station’s network
administrator:
• An IP address
• Port number
• Receiver number
• Line number
Notes
• CID is the only format that can be transmitted to the CMS over an Ethernet
network.
• You must enter a different port number for each account. If you enter the
same port number for multiple accounts, the panel will enable one account
and disable all others.
• No two accounts can have the same IP address or port number.
• Outputs activation state will not be sent to CMS.
Table 34: CMS network (transmitter) programming options
Option
Description
Enabled
Yes: Enables the CMS network operation
No: Disables the CMS network operation