In-suite signal silence applications – Edwards Signaling eFSA250 User Manual
Page 277

Appendix D: Applications
E-FSA64 and E-FSA250 Technical Reference Manual
265
Message Line 1: 24VDC_RISER
Message Line 2: SOUNDER_RLY_1
5. Configure Correlation 001 as follows:
Add/Remove Device: All alarm signal-initiating devices
Add/Remove NAC: All RLY modules used to active sounder bases
In-suite signal silence applications
This section provides high level instructions for creating an in-suite signal silence
application based on the use of correlation groups. Additional background
material and detailed instructions are also available. See:
• “What is in-suite signal silence?” on page 34
• “Programming in-suite signal silence” on page 92
• “What is a correlation group?” on page 32
• “Correlation group programming” on page 86
Figure 60: Building with a separate audible circuit for each floor and separate circuits for
audibles within and not within dwelling units
NAC 1
NAC 2
NAC 8
NAC 7
NAC 9
NAC 10
NAC 6
NAC 5
NAC 4
NAC 3
Floor 5
Floor 4
Floor 3
Floor 2
Floor 1
Rooms
Hallways