Chapter 5: Diagnostics, maintenance, and testing
202
E-FSA64 and E-FSA250 Technical Reference Manual
• Input zones programmed as waterflow with retard require 10 to 15 seconds of
activation to initiate the test signals.
• Devices programmed as alarm verify and not in test mode go directly into
alarm if activated (the alarm verification process is bypassed).
• Restore each device after testing. For example, if you are testing a pull
station, reset the pull station before testing the next device.
The panel terminates walk test if:
• The zone or device being tested remains inactive for 30 minutes.
• The walk test is stopped by the user.
To start a walk test:
1. Press the Menu button and choose Test.
2. Choose Walk Test Silent or Walk Test Audible.
3. Enter a level one password.
4. Choose either All Devices or Zone.
5. If you chose Zone, enter the zone ID for the zone
you are going to conduct the walk test.
6. Choose Start.
7. Conduct your walk test.
8. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Note:
To see the activation and restoration of all walk
test events, the panel must be reset prior to ending
the walk test. Once the reset is complete, you can
end the walk test and view a walk test report.
Main Menu
Reports
Test
Control
Program
Test
Walk Test Silent
Walk Test Audible
Test Fire
Enter Password
0000
Walk Test Sil/Aud
All Devices
Zone
Zone
Number 01
Zone 01
Start
End
To end a walk test:
1. Press the Menu button and choose Test.
2. Choose Walk Test Silent or Walk Test Audible.
3. Choose either All Devices or Zone.
4. If you chose Zone, enter the zone ID of the zone
for which you are going to end the walk test.
Main Menu
Reports
Test
Control
Program
Test