Edwards Signaling eFSA250 User Manual
Page 280

Appendix D: Applications
268
E-FSA64 and E-FSA250 Technical Reference Manual
Creating an in-suite correlation group
The in-suite correlation is used to silence sounders inside dwelling units, except
on the floor of alarm.
Create one in-suite correlation group. On the input side, add all input devices on
all floors. Include those located inside dwelling units and those located in
hallways.
On the output side, add all sounders located inside dwelling units on all floors.
Notes
• Set the alarm activation count for this correlation to 1.
• For this correlation only, enable in-suite signal silence.
In-Suite Signal Silence Correlation
Input
Output
Occupant and hallway inputs on all floors
Occupant sounders on all floors
How this application works
This application silences the audible alarm signals inside dwelling units, except
on the floor of the alarm.
For example, if an alarm occurs on the third floor:
• The Floor 3 Correlation turns on the sounders on the floor of the alarm
(including those inside dwelling units).
• The Hallway Correlation turns on hallway sounders throughout the building.
• The In-Suite Signal Silence Correlation turns on sounders in residences on all
other floors.
• After 60 seconds, the In-Suite Signal Silence Correlation, which has in-suite
signal silence enabled, silences sounders inside dwelling units on all other
floors. These signals remain off until the in-suite signal silence timer expires
or a subsequent alarm comes in.