Sa-dact testing – Edwards Signaling eFSA250 User Manual
Page 211

Chapter 5: Diagnostics, maintenance, and testing
E-FSA64 and E-FSA250 Technical Reference Manual
199
2. Choose Test Fire.
3. Enter a level one password.
4. Choose the loop the device is on.
Note:
If the panel only has one loop, the loop
selection screen does not display. Go to the next
step.
5. Enter the device number of the device you want to
test fire.
6. Press Enter.
7. Choose Start to start the test.
8. When you have finished, press Reset (or repeat
steps 1 to 7 and choose End) to clear the test
alarms and return the system to normal.
9. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Test
Control
Program
Test
Walk Test Silent
Walk Test Audible
Test Fire
Enter Password
0000
Test Fire
Loop 01<>
Test Fire
001
Device 001
Test Fire 001
Start
End
SA-DACT testing
A dialer test is a test of the telephone line for each dialer account. When a dialer
is tested, a normal or abnormal test message (depending on the state of the
system) is sent to the selected account. If the dialer is set up for dual line
operation, a test message is sent to both lines regardless of the success of the
transmission for either account.
Note:
Before conducting a test, configure the dialer’s accounts for proper
operation.
To conduct a dialer test:
1. Press the control panel’s Menu button.
2. Choose Test.
3. Choose Dialer.
4. Enter a level one password.
5. Select the account that you want to test.
6. Press Enter.
Main Menu
Reports
Test
Control
Program
Test
Walk Test Audible
Test Fire
Dialer