Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
39
Default loop configuration settings
• Loop class: Class B
• Zone
Type: Alarm
Correlation group: 001
Notes
- By default, NACs, zones, and most
devices are assigned to correlation
group 001.
- Relay and sounder bases with the
Follow option set to Head are not
automatically assigned to correlation
groups.
Event notification
Active > Printer: Yes
Active > Dialer: Acct 1
Active > NET (1-8): No
Active > CID: 110
Trouble > Printer: Yes
Trouble > Dialer: Acct 1
Trouble > NET (1-8): No
Trouble > CID: 373
Disable > Printer: Yes
Disable > Dialer: Acct 1
Disable > CID: 570
Disable > NET (1-8): No
Pre alarm > Printer: Yes
Pre alarm > Dialer: None
Pre alarm > NET (1-8): No
Pre alarm > CID: 118
Alarm verify > Printer: Yes
Alarm verify > Dialer: None
Alarm verify > NET (1-8): No
Alarm verify > CID: 118
Maintenance alert > Printer: Yes
Maintenance alert > Dialer: Acct 1
Maintenance alert > NET (1-8): No
Maintenance alert > CID: 393
Test > Printer: Yes
Test > Dialer: Acct 1
Test > CID: 614
Test > NET (1-8): No
• Correlation Groups
Add/remove zone > Zone: 01
Add/remove zone > Status: Included
Add/remove NAC > Panel NAC: 1
Add/remove NAC > Status: Included
Add/remove device > Device: 001
Suite signal silence: No
Activation count > Number: 01
Copy > From group: 001
Delay > Time: 000
• Device
Alt Operation: Yes
Day sensitivity: Least
Night sensitivity: Least
Day prealarm %: Off
Night prealarm %: Off
Base follow: Alarm
Zone: Off
Event notification
Active > Printer: Yes
Active > Dialer: Acct 1
Active > NET (1-8): No
Active > CID: 110
Alarm verify > Printer: Yes
Alarm verify > Dialer: None
Type (input device): Depends on type of
device and marketplace
Type (output device): Genesis with
audible/visible silence
Correlation group: 1