Genesis High Candela Ceiling Speaker-Strobe
Installation Sheet
Description
The Genesis High Candela Ceiling Speaker-Strobe is a fire
alarm notification appliance designed for indoor ceilings and
walls. See Table 1 for a list of model numbers.
Table 1: Models
Description
Number
Speaker-Strobe,
25 VRMS, 95 to 177 multi-cd,
white
ADTGC-S2VMH
MGC-S2VMH
EGC-S2VMH
XLSGC-S2VMH
GC-S2VMH
ZGC-S2VMH
Speaker-Strobe,
25 VRMS, 95 to 177 multi-cd,
white, with FIRE marking
ADTGCF-S2VMH MGCF-S2VMH
EGCF-S2VMH
XLSGCF-S2VMH
GCF-S2VMH
ZGCF-S2VMH
Speaker-Strobe,
70 VRMS, 95 to 177 multi-cd,
white
ADTGC-S7VMH
MGC-S7VMH
EGC-S7VMH
XLSGC-S7VMH
GC-S7VMH
ZGC-S7VMH
Speaker-Strobe,
70 VRMS, 95 to 177 multi-cd,
white, with FIRE marking
ADTGCF-S7VMH MGCF-S7VMH
EGCF-S7VMH
XLSGCF-S7VMH
GCF-S7VMH
ZGCF-S7VMH
A field configurable jumper option is available for selecting the
desired strobe signal output.
The speaker-strobe includes field configurable switches for
selecting the desired candela and wattage outputs. These
output settings lock in place and remain visible after final
installation.
This strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971 Signaling
Devices for the Hearing Impaired and the latest Canadian
standard CAN/ULC-S526. Synchronized operation requires a
separately installed synchronization control module. See
Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements
in the latest editions of the NFPA codes and standards and
Canadian Electrical Code, Part 1, Section 32 and
CAN/ULC-S524, Standard for the Installation of Fire Alarm
Systems, and in accordance with the local authorities having
jurisdiction.
Table 2: Compatible synchronization module models
Model name
Number
Auto-Sync Output Module
SIGA-CC1S
SIGA-MCC1S
GSA-CC1S
GSA-MCC1S
Genesis Signal Master -
Remote Mount
ADTG1M-RM MG1M-RM
EG1M-RM
XLSG1M-RM
G1M-RM
ZG1M-RM
Installation
WARNING
: To reduce the risk of shock, disconnect all power
and allow 10 minutes for stored energy to dissipate before
handling.
Caution
: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field
wires around the terminals.
Note:
When installed, these devices are not centered on the
electrical box. Make sure boxes are mounted to compensate
for this difference. See Figure 7.
To install the speaker-strobe:
1. Open the cover by depressing the tab on the side of the
unit with a small screwdriver. Hinge the cover down, to
access the mounting screws and selectable candela and
wattage switches. The cover is also detachable for
installation convenience.
2. If temporal strobe (private mode) operation is desired, cut
jumper JP1. See Figure 2.
3. Connect the speaker and strobe terminals to the signal
circuit field wiring. For the unit to function properly,
observe polarity. See Figure 4.
4. Slide the candela switch to the desired candela output (95,
115, 150, or 177 cd) by aligning it with the indicator below
the switch. See Figure 1.
5. Slide the wattage switch to the desired wattage tap (2 W,
1 W, 1/2 W, or 1/4 W) by aligning it with the indicator
below the switch. See Figure 1.
6. Mount the unit onto a compatible electrical box. See
Figure 5.