Edwards Signaling eFSA250 User Manual
Page 126

Chapter 2: Front panel programming
114
E-FSA64 and E-FSA250 Technical Reference Manual
Table 31: Annunciator options
Option
Description
Annunciator type
Set annunciator type to:
Off: No annunciator is connected. If type is set to Off, Number
expanders, Label, and Reporting configuration are not available.
LCD-C: The annunciator has a display and common controls
LCD: The annunciator has a display only (no common controls)
LED: The annunciator has LEDs and common controls (no
display)
Graphic: Graphics controller interface for the Envoy graphics
board
Expanders
Set expanders to None, 1, or 2. This is the number of LED
expander modules you are using with the annunciator.
Label
Enter a text label for the annunciator (two lines of 20
characters). When you have finished, choose Save.
Event notification
Set the trouble event information by setting the notification
information. When you have finished, choose Save. See
“Factory default settings” on page 36 for annunciator event
notification default settings.
Printer: Yes or No. This controls whether event information is
sent to the printer
Dialer:
• Acct 1 2: Event information is sent to both dialer accounts
• Acct 1: Event information is sent to dialer account one
• Acct 2: Event information is sent to dialer account two
• None: Event information is not sent to the dialer
CID: Contact ID event code (000 to 999)
NET (1-8): Yes or No. Controls whether event information is
sent to the connected network