Setting up the programmable keys – Edwards Signaling eFSA250 User Manual
Page 64

Chapter 2: Front panel programming
52
E-FSA64 and E-FSA250 Technical Reference Manual
Note:
The current language, marketplace, and loop device configuration settings
are not affected by the Restore Defaults command.
To restore the default settings:
1. Press the Menu button and choose Program.
2. Choose Restore Defaults.
3. Enter a level two password.
4. Select either Panel Only, CMS Only, or Panel and
CMS.
Panel only: Restores only the panel’s defaults
(panel operation and panel configuration options)
CMS only: Restores only the dialer, network (1-8)
Panel and CMS: Restores both the panel and
CMS device defaults
5. Press Enter.
6. Return to the Program menu.
7. Choose Panel Restart.
8. Choose Yes.
The panel restarts, and the factory default settings
are reloaded into the database.
Main Menu
Reports
Test
Control
Program
Program
Clear History
Password
Restore Defaults
Enter Password
0000
Restore Defaults
Panel Only
CMS Only
Panel and CMS
Setting up the programmable keys
There are two control panel buttons that can be assigned to correlation groups in
order to:
• Disable and reenable panel NACs, devices, and zones
• Activate panel NACs and devices
• Restore panel NACs and devices
• Unlatch all output devices globally
Notes
• You cannot disable a NULL device when it is part of a correlation group.
• You cannot configure user keys for correlation groups.