Event id numbers and descriptions – Edwards Signaling eFSA250 User Manual
Page 166

Chapter 3: System operation
154
E-FSA64 and E-FSA250 Technical Reference Manual
Event ID numbers and descriptions
Table 43: Event ID numbers and descriptions
ID
Event description
000 Loop 1 initialization:
Loop 1 is starting
up
001 Loop 1 fault: A short or open was
detected on loop 1 affecting the
communications between the panel and
the devices on the loop
002 Not used
003 Loop 1 card fault: The loop 1 card is not
present or it is not working properly
004 Loop 1 uncfgrd alarm: A device on loop
1 that is not programmed went into
alarm
005 Loop 1 uncfgrd trouble: A device on
loop 1 that is not programmed went into
trouble
006 Not used
007 Loop 1 over limits: There are too many
devices on loop 1
008 Loop 1 device 000: A device on loop 1
has an address set to zero
009 Not used
ID
Event description
010 Loop 2 initialization:
Loop 2 is starting
up
011 Loop 2 fault: A short or open was
detected on loop 2 affecting the
communications between the panel and
the devices on the loop
012 Not used
013 Loop 2 card fault: The loop 2 card is not
present or it is not working properly
014 Loop 2 uncfgrd alarm: A device on loop
2 that is not programmed went into
alarm
015 Loop 2 uncfgrd trouble: A device on
loop 2 that is not programmed went into
trouble
016 Not used
017 Loop 2 over limits: There are too many
devices on loop 2
018 Loop 2 device 000: A device on loop 2
has an address set to zero
019 Not used