beautypg.com

Edwards Signaling Genesis Strobe User Manual

Genesis strobe, Product information, Specifications

background image

Installation Sheet

07OCT05

P/N: 3100559 REV: 3.0

Genesis Strobe

1 / 2

Genesis Strobe

Product information

The Genesis Strobe is a visible fire alarm notification appliance
designed for indoor walls. See Table 1 for a list of model
numbers.

The strobe includes a field configurable switch for selecting the
desired candela output and a field configurable jumper for the
strobe signal output. The candela output setting is locked in
place and remains visible after final installation.

This strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971 Signaling
Devices for the Hearing Impaired
and the latest Canadian
standard CAN/ULC S526-02. Synchronized operation requires
a separately installed synchronization control module. See
Table 2 for a list of compatible synchronization modules.

Install this device in accordance with applicable requirements
in the latest editions of the NFPA codes and standards and
Canadian Electrical Code, Part 1, Section 32, CAN/ULC S524-
01, Standard for the Installation of Fire Alarm Systems, and in
accordance with the local authorities having jurisdiction.

Table 1: Models

Description Model

number

Strobe,
15 to 110 multi-cd,
white

ADTG1-VM

MG1-VM

EG1-VM

XLSG1-VM

G1-VM

ZG1-VM

G1-VM-LG

Strobe,
15 to 110 multi-cd,
white, with FIRE marking

ADTG1F-VM

MG1F-VM

EG1F-VM XLSG1F-VM
G1F-VM

ZG1F-VM

G1F-VM-LG

Strobe,
15 to 110 multi-cd,
red

ADTG1R-VM

MG1R-VM

EG1R-VM XLSG1R-VM
G1R-VM

ZG1R-VM

G1R-VM-LG

Table 1: Models

Description Model

number

Strobe,
15 to 110 multi-cd,
red, with FIRE marking

ADTG1RF-VM MG1RF-VM

EG1RF-VM

XLSG1RF-VM

G1RF-VM ZG1RF-VM
G1RF-VM-LG

Trim plate,
white

ADTG1T

MG1T

EG1T

XLSG1T

G1T

ZG1T

G1T-LG

Trim plate,
white, with FIRE marking

ADTG1T

MG1T

EG1T

XLSG1T

G1T

ZG1T

G1T-LG

Trim plate,
red

ADTG1RT MG1RT
EG1RT

XLSG1RT

G1RT

ZG1RT

G1RT-LG

Trim plate,
red, with FIRE marking

ADTG1RT MG1RT
EG1RT

XLSG1RT

G1RT

ZG1RT

G1RT-LG

Table 2: Compatible synchronization modules

Description Model

number

Auto-Sync Output
Module

SIGA-CC1S

SIGA-MCC1S

SIGA-CC1S-LG SIGA-MCC1S-LG

Genesis Signal Master
Snap-on Mount

ADTG1M MG1M
EG1M

XLSG1M

G1M ZG1M
G1M-LG

Genesis Signal Master -
Remote Mount

ADTG1M-RM MG1M-RM
EG1M-RM XLSG1M-RM
G1M-RM ZG1M-RM
G1M-RM-LG

Specifications

Operating voltage: 24 Vdc or 24 Vfwr, nominal
Strobe operating current: See Table 3
Light output: Selectable at 15, 30, 75, and 110 cd

Synchronization: Meets UL 1971 requirements. Maximum

allowed resistance between any two devices is 20

Ω.

Refer to specifications for the synchronization control

module, this strobe, and the control panel to determine

allowed wire resistance.

Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm)
Compatible electrical boxes

North American 2-1/2 in (64 mm) deep 1-gang box
Standard 4 in square box 1-1/2 in (38 mm), 2-gang, or 4 in
octagonal with G1T or G1RT trim accessory

Operating environment

Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 0 to 93% RH, noncondensing at 90 °F (32 °C)