Disabling and enabling loop events – Edwards Signaling eFSA250 User Manual
Page 185

Chapter 3: System operation
E-FSA64 and E-FSA250 Technical Reference Manual
173
To disable or enable a panel event:
1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Enable/Disable.
4. Choose Panel Event.
5. Enter the ID number of the event type to disable or
enable.
See “Event ID numbers and descriptions” on page
154 for event descriptions and the list above for
the events that can be disabled.
6. Press Enter.
7. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Main Menu
Reports
Test
Control
Program
Enter Password
0000
Control
Enable/Disable
Activate/Restore
Enable/Disable
Device
Zone
Panel Event
Panel Event Disable<>
034
Event 034
When you disable an event:
• The common Disable LED turns on
• The common Trouble LED flashes and the panel goes into a trouble state
• The common Trouble relay changes state
• The disabled and active points indicators on the LCD increment
• The LCD displays a message indicating that the event is disabled.
Disabling and enabling loop events
Disabling a loop event prevents it from being displayed, printed, or reported off
premises. This is typically done during maintenance. For example, you might
want to disable the Loop 1 unconfigured alarm event, if you are switching out a
detector. Remember to enable the event as soon as you have finished working.
When you disable a loop event:
• The common Disable LED turns on
• The common Trouble LED flashes and the panel goes into a trouble state
• The common Trouble relay changes state