Edwards Signaling 105XBRi Series User Manual

Installation instructions for rebel chameleon

background image

Installation Instructions for Rebel Chameleon

TM

105XBRi Series LED Multi-Status Indicator in

NEMA 4X Enclosures

Description

The 105XBRi Series Chameleon Multi-Status LED Indicator

is a UL and cUL listed, multi-color LED signaling appliance

which, when assembled in accordance with these installa-

tion instructions, constitute a UL Listed Type 4X enclosure

and are UL Listed for Marine Use. They are designed for

use in industrial applications or in applications where a Type

4X enclosure is required. When assembled in accordance

with these instructions, the 105XBRi series visual signals

are UL Listed for use in Division 2 Hazardous Locations as

described in Table 1.
The lights are available in 24V DC and 120V 50/60 Hz. They

are available in either Red/Blue/Amber or Red/Green/Amber.
Edwards Signaling's NEW 105XBRi Multi-status Indicator

is more "chameleon-like" than ever. With our new adaptive

design - one device does it all. With a quick change to the

new 105 Chameleon's dip switch settings, these flexible

multi-status indicators instantly adapt for use with or without

control from an external PLC, PAC, or control relay. Now,

regardless of the application you will have just the right device

for the job with only half the inventory.

XTRA-SAFE Enabled
The Chameleon 105XBRi devices ship as standard with

Edwards Signaling's XTRA-SAFE

TM

Technology (patent

pending) Enabled. XTRA-SAFE multi-status indicating

devices employ patented combinations of color AND flash-

rate to provide more definite status indication to those who

are color-blind. With XTRA-SAFE, when Chameleon multi-

status indicators are turned red, they pulse at a rate of 240

flashes per minute, further emphasizing the urgency which

the color red typically connotes. When amber, these devices

pulse at a "less urgent" rate of 120 flashes per minute. When

Chameleon multi-status indicators are turned blue or green

and no other colors are energized, the Chameleon devices

remain "steady-on" and do not flash. Even in extreme cases

where no color is perceived, flash-rate variation provides a

redundant layer of visual indication.

P/N 3101612 ISSUE 3

© 2010

http://www.edwardssignaling.com Phone: (800) 336-4206 Fax: (800) 454-2363

When XTRA-SAFE Technology is enabled, and multiple col-

ors are energized, the device will cycle through the energized

colors at the following pre-set flash-rates:

Red: 240 FPM

Amber: 120 FPM

Green or Blue: 65 FPM

XTRA-SAFE Disabled
While in most cases, the added layer of safety gained by op-

erating a multi-status indicator with XTRA-SAFE Technology

is desirable, some applications may not require differentiation

in flash rates. In other applications, changes do not corre-

spond to escalating levels of urgency. The adaptive design

of the new Chameleon 105 XBRi allows the product to be

adapted to accommodate these requirements by configuring

the dipswitches as shown in Figure 1 (Applications WITH-

OUT a separate PLC or Controller - XTRA-SAFE Technology

Disabled). With XTRA-SAFE Disabled, when red or amber,

the unit pulses at a rate of 65 flashes per minute. When

Chameleon multi-status indicators are turned green or blue

and no other colors are energized, the Chameleon devices

remain "steady on" and do not flash.
When XTRA-SAFE Technology is disabled, and multiple col-

ors are energized, the device will cycle through the energized

colors at 65 FPM.
Externally Controlled
The Chameleon multi-status indicators can also be used in

applications where they will be controlled "externally" us-

ing a Programmable Logic Controller (PLC) or other such

external controller. When externally controlled by a PLC,

activation of colors and flash-rate are fully customizable,

and can be programmatically determined. In applications,

where multiple colors are activated simultaneously, the lights

operate on a priority with red highest, amber second and blue

or green, the lowest. Refer to Figure 1 (Applications WITH

a separate PLC or Controller).Wire color corresponds with

each indicated color.

Red wire = Red LED's

Yellow wire = Amber LED's

Blue with Green tracer wire = Green or Blue LED's

Table 1. Hazardous Location Ratings

Cat. No.

Class

Division

Group

Operating Temperature

105XBRiRGA24D

105XBRiRGA120A

I

2

A, B, C, D

T5 (100C, 212F)

II

2

F, G

T5 (100C, 212F)

III

T5 (100C, 212F)

105XBRiRBA24D

105XBRiRBA120A

I

2

A, B, C, D

T6 (85C, 185F)

II

2

F, G

T6 (85C, 185F)

III

T6 (85C, 185F)