Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
47
Device type
Description
Relay silence NC
For relays that open when activated and close when you press Signal
Silence.
Relay silence NO
For relays that close when activated and open when you press Signal
Silence.
Supervised output
For modules that output an unsynchronized signal and that do not
turn off when you press Signal Silence.
Supervised output
(latched)
For latched output modules that output an unsynchronized signal and
that do not turn off when you press Signal Silence.
Unlatch outputs
For output modules that are configured to manually unlatch latched
outputs [1]
[1] The following output modules can be configured to unlatch latched outputs: E-ISO, E-IDC1A,
E-IDC1B, or E-IDC2B.
Table 16: NAC modules
Device type
Description
Genesis audible/visible
silence
For Genesis and Enhanced Integrity horns and strobes. Genesis and
Enhanced Integrity appliances maintain synchronization per UL 1971.
For Genesis devices only, connected horns can be silenced and
strobes turn off.
Genesis non-silence
For Genesis and Enhanced Integrity horns and strobes. Genesis and
Enhanced Integrity appliances maintain synchronization per UL 1971.
For Genesis devices only, connected horns cannot be silenced and
strobes on the same two-wire circuit flash until the panel is reset.
Genesis audible silence
For Genesis and Enhanced Integrity horns and strobes. Genesis and
Enhanced Integrity appliances maintain synchronization per UL 1971.
For Genesis devices only, it allows connected horns to be silenced
while strobes on the same two-wire circuit continue to flash until
panel reset.
Continuous silenceable
For strobes and notification appliances that self-generate a temporal
pattern
Continuous non-
silenceable
For strobes and notification appliances that self-generate a temporal
pattern
Supervised
Lets you connect supervisory devices, such as a relay device or
switch
City tie
Outputs an unsynchronized, 24-volt continuous (steady) signal that
cannot be silenced or disabled. Select this NAC type when the NAC
is connected to a city tie module.