Edwards Signaling Genesis Chime User Manual
Genesis chime, Product information, Specifications
Installation Sheet
27MAY03
P/N: 3100561 REV: 1.0
Genesis Chime
1 / 2
Genesis Chime
Product information
The Genesis Chime is an audible fire alarm notification
appliance designed for indoor walls. See Table 1 for a list of
model numbers.
The chime includes field configurable jumper options for
selecting the desired dB output, steady or temporal chime
output, and constant non-coded voltage or single-stroke coded
voltage operation. A Genesis Signal Master is required when
chimes are configured for coded operation. See Table 2 for a
list of compatible synchronization modules.
Install this device in accordance with applicable requirements
in the latest editions of the NFPA codes and standards and in
accordance with the local authorities having jurisdiction.
Table 1: Model numbers
Model description
Model numbers
Chime,
white
ADTG1-C MG1-C
EG1-C
XLSG1-C
G1-C ZG1-C
G1-C-LG
Chime,
white, with FIRE marking
ADTG1F-C MG1F-C
EG1F-C
XLSG1F-C
G1F-C
ZG1F-C
G1F-C-LG
Chime,
red
ADTG1R-C MG1R-C
EG1R-C
XLSG1R-C
G1R-C
ZG1R-C
G1R-C-LG
Chime,
red, with FIRE marking
ADTG1RF-C
MG1RF-C
EG1RF-C XLSG1RF-C
G1RF-C
ZG1RF-C
G1RF-C-LG
Trim plate,
white
ADTG1T
MG1T
EG1T
XLSG1T
G1T
ZG1T
G1T-LG
Table 1: Model numbers
Model description
Model numbers
Trim plate,
red
ADTG1RT MG1RT
EG1RT
XLSG1RT
G1RT
ZG1RT
G1RT-LG
Table 2: Compatible synchronization modules
Model names
Model numbers
Auto-Sync Output
Module
SIGA-CC1S
SIGA-MCC1S
SIGA-CC1S-LG SIGA-MCC1S-LG
Signal Master
snap-on piggyback
(1-gang)
ADTG1M MG1M
EG1M
XLSG1M
G1M ZG1M
G1M-LG
Signal Master - Remote
Mount
ADTG1M-RM MG1M-RM
EG1M-RM XLSG1M-RM
G1M-RM ZG1M-RM
G1M-RM-LG
Note: Synchronization module requirements are determined by
your application
Specifications
Operating voltage
Regulated 16 to 33 Vdc, 16 to 33 Vfwr
This device was tested to the regulated 24 Vdc/fwr
operating voltage limits of 16 V and 33 V. Do not apply
80% and 110% of these values for system operation.
Operating current: See Table 2
Sound level output: See Table 3
Signals
Steady: 60 strokes per minute
Temporal: 3-stroke pattern
Coded: Maximum 60 strokes per minute
Operating modes
Non-coded: Continuous voltage
Coded: Single-stroke controlled by voltage
Default settings
Signal: Steady
Sound level output: High db
Operation: Non-coded
Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm)
Compatible electrical boxes
North American 2-1/2 in (64 mm) deep 1-gang box
Standard 4 in square box 1-1/2 in (38 mm), 2-gang, or 4 in
octagonal with G1T or G1RT trim accessory
Operating temperature range: 32 to 120 °F (0 to 49 °C)
Operating humidity range: 0 to 93% RH
Agency listings: Meets or exceeds UL464 Seventh Edition for
private mode